ACMV Pro / Tool guide

TOOL GUIDE

Head loss & pump sizing

Calculate pump head and power for closed/open water systems from path losses and outlet requirements.

Purpose & scope

Calculate pump head and power for closed/open water systems from path losses and outlet requirements.

Closed-loop circulation excludes building elevation. Open systems assume an atmospheric source; pressurized source effects and NPSH are not calculated.

Inputs

Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.

ParameterValue / interpretation
Proposed pump typeNot specified / End-suction centrifugal / Inline centrifugal / Double-suction centrifugal / Multistage
ApplicationChilled-water circulation / Condenser water / Water supply / pressure boosting
System typeChiller / closed loop / Water supply / open system
Pump flow · m³/hVolumetric flow at the calculation location; check the selected unit.
Water temperature · °CWater temperature used for fluid properties.
Pipe roughness · mmAbsolute roughness of the internal pipe/duct surface, in mm.
Elevation from source to outlet · mSource-to-outlet elevation for open systems; excluded from closed-loop circulation head.
Required outlet residual pressure · kPaRequired residual pressure at the outlet of an open system, in kPa.
Additional head · mH₂OAdditional losses not included in path rows; avoid double counting.
Head allowance · %Allowance applied to the result; not a substitute for entering all losses.
Pump efficiency · %Fan/pump efficiency at duty, from manufacturer data.
Motor efficiency · %Motor efficiency used to estimate electrical input power.

Steps

  1. Select closed/open system and enter flow, temperature, roughness and efficiencies.
  2. For closed loops include supply and return; use internal diameter and equipment Δp in kPa.
  3. For open systems enter elevation and residual pressure. Verify Q–H, NPSH, operating range and motor against catalogue data.

Worked example

This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.

Examples use a decimal point and no thousands separator.

All example inputs
ParameterValue / interpretation
Proposed pump typeNot specified
ApplicationChilled-water circulation
System typeChiller / closed loop
Pump flow10 m³/h
Water temperature7 °C
Pipe roughness0.045 mm
Elevation from source to outlet15 m
Required outlet residual pressure100 kPa
Additional head0 mH₂O
Head allowance10 %
Pump efficiency65 %
Motor efficiency90 %

Replace the default path with exactly this row; delete the other sample rows.

ParameterValue / interpretation
SectionExample calculation path
Section flow10 m³/h
Section dimensionsD 65 mm
Section length60 m
Total fitting K2
Equipment pressure loss30 kPa

Expected results (rounded)

ParameterValue / interpretation
Pump head4.32 mH₂O
Shaft power0.181 kW

Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.

Method & limitations

Closed-loop circulation excludes building elevation. Open systems assume an atmospheric source; pressurized source effects and NPSH are not calculated.

Enter consecutive sections of the critical path, including supply and return in closed loops. Do not sum parallel branches.

H = Σ(f·L/D + K)·v²/(2g) + equipment head. Closed loops exclude building height from circulation head; fill pressure must be checked separately. Open systems add elevation and residual pressure, assuming an atmospheric source and negligible endpoint velocity-head difference.

Pure water only; not a glycol model. The motor size is a shaft-power guide; verify the pump curve, NPSH, duty point and operating range.

Common mistakes

Adding building height to a closed loop; confusing DN/internal D or kPa/mH₂O; ignoring source pressure and NPSH.

Projects & reports

  1. Choose or create an engineering project and enter your actual design inputs.
  2. Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
  3. Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.

Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.

References & related tools

Caleffi — Hydronic operating conditions

The tool implements the methods and limits stated above; linking a standard does not establish complete compliance with that standard.