Psychrometric chart

Determine moist-air properties, compare A/B states, heat-transfer rate and dry-air-based mixing.

Purpose & scope

Determine moist-air properties, compare A/B states, heat-transfer rate and dry-air-based mixing.

Dry bulb −20…60 °C, pressure 60…110 kPa. Supersaturated mixture condensation/fog separation is not modelled; below 0 °C equilibrium is over ice.

Inputs

Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.

ParameterValue / interpretation
Atmospheric pressure · kPaLocal absolute atmospheric pressure for air properties.
Input property pair · kPaSelect the second property paired with dry bulb; the next field’s units follow that choice.
Dry-bulb temperature · °CDry-bulb temperature of the selected state A or B.
Relative humidity · %Second property value: RH %, wet/dew point °C, humidity ratio g/kgda or enthalpy kJ/kgda.
Dry-air mass flow · kg/sDry-air mass flow for A → B, in kg/s.
Stream A fraction in mixture · %Dry-air mass fraction of stream A in the A+B mixture, in %.

Steps

  1. Enter atmospheric pressure and select the input property pair for A.
  2. Switch to B, enter its properties and enable the desired RH, enthalpy, wet-bulb or specific-volume lines.
  3. Enter dry-air mass flow and stream A fraction; inspect process results, mixture M and the report.

Worked example

This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.

Examples use a decimal point and no thousands separator.

All example inputs
ParameterValue / interpretation
A26 °C / 50% RH
B35 °C / 65% RH
Atmospheric pressure101.325 kPa
Mass flow1 kg/s dry air
A fraction50% A

Expected results (rounded)

ParameterValue / interpretation
Humidity ratio A10.5 g/kgda
Enthalpy A52.91 kJ/kgda
Heat transfer rate A → B42.07 kW
Mixture M temperature30.55 °C

Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.

Method & limitations

Dry bulb −20…60 °C, pressure 60…110 kPa. Supersaturated mixture condensation/fog separation is not modelled; below 0 °C equilibrium is over ice.

The horizontal axis is dry-bulb temperature; the vertical axis is humidity ratio per kg of dry air. The boundary curve is 100% RH saturation. Toggle relative humidity, enthalpy, wet-bulb and specific-volume lines. Chart temperature range: −20 to 60 °C; the humidity axis expands to include valid points.

Saturation vapor pressure follows Hyland–Wexler/ASHRAE. W = 0.621945·Pv/(P−Pv); h = 1.006·T + W(2501 + 1.86·T). Wet bulb and dew point are solved iteratively. Below 0 °C, saturation and dew point use equilibrium over ice (frost point).

Total heat A → B = ṁda(hB−hA); water added/removed = ṁda(WB−WA). Mixing balances enthalpy and water vapor using dry-air mass fractions. Supersaturated mixtures are flagged; condensation or fog separation is not modeled. RH = 0 has no finite dew point.

ASHRAE — Psychrometrics

Common mistakes

Confusing g/kgda humidity ratio with RH%; entering volumetric flow as kg/s; treating A–B as a simulated coil process; misreading heat-transfer sign.

Projects & reports

  1. Choose or create an engineering project and enter your actual design inputs.
  2. Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
  3. Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.

Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.

References & related tools

ASHRAE — Psychrometrics

The tool implements the methods and limits stated above; linking a standard does not establish complete compliance with that standard.