ACMV Pro / Tool guide

TOOL GUIDE

Cooling load & AC sizing

Estimate a room’s sensible and latent cooling loads and check equipment capacity against both components.

Purpose & scope

Estimate a room’s sensible and latent cooling loads and check equipment capacity against both components.

Single-room steady-state estimate, not hourly HB/RTS. BTU/h sizes are references; verify actual equipment sensible/latent capacities.

Inputs

Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.

ParameterValue / interpretation
Floor area · m²Room floor area for volume, lighting load and area-based rates.
Room height · mClear room height used for room volume.
Indoor temperature · °CTarget room air temperature.
Indoor humidity · %Relative humidity of the room air.
Outdoor temperature · °COutdoor air temperature at the design condition.
Outdoor humidity · %Relative humidity of the outdoor air.
Atmospheric pressure · kPaLocal absolute atmospheric pressure for air properties.
Net opaque external wall area · m²Outdoor-facing opaque wall area, excluding glazing.
Wall heat transfer coefficient · W/m²KLower values mean better insulation. Unit: W/m²K.
Wall solar equivalent rise · KSelect the material/system appropriate to the actual application; verify reference values.
Exposed roof area · m²Outdoor-exposed roof area; enter 0 if this room has no exposed roof.
Roof heat transfer coefficient · W/m²KLower values mean better insulation. Unit: W/m²K.
Roof solar equivalent rise · KSelect the material/system appropriate to the actual application; verify reference values.
External glazing area · m²Outdoor-facing glazing area.
Glazing heat transfer coefficient · W/m²KLower values mean better insulation. Unit: W/m²K.
Incident solar irradiance · W/m²Solar irradiance incident on glazing at the design orientation/time.
Solar heat fraction through glazingRange 0–1. A value of 0.5 means 50% of incident solar heat enters through the glazing.
Solar fraction remaining after shadingRange 0–1: 1 means unshaded, 0 means fully shaded in this estimate.
Occupants · peopleSimultaneous occupants at the design condition.
Sensible heat per person · WSensible heat gain per occupant for the activity level.
Latent heat per person · WLatent heat gain from each occupant’s moisture emission.
Lighting power density · W/m²Lighting power per floor area, multiplied by room floor area.
Equipment heat gain · WEquipment heat gain in the room before the use factor.
Simultaneous equipment use fractionA value of 0.8 means 80% of equipment heat gain occurs simultaneously.
Outdoor air entering room · m³/hOutdoor air supplied directly to the room, excluding infiltration.
Air changes per hour from infiltration · 1/hA value of 0.3 means infiltration per hour equals 30% of room volume; excludes outdoor-air ventilation.
Other sensible gains · WAdditional sensible gains not included above.
Other latent gains · WAdditional latent gains not included above.
Design allowance · %Allowance applied to both sensible and latent loads.
Number of AC units · unitsAC unit count sharing the load equally for reference sizing.
Temperature-cooling / total cooling capacity ratioA value of 0.75 means 75% temperature cooling and 25% dehumidification. Use equipment data.
Actual / nameplate AC capacity ratioA value of 0.9 means 90% of nameplate capacity at design conditions. Use equipment selection data.

Steps

  1. Enter room size, indoor/outdoor conditions and actual wall, roof and glazing areas.
  2. Enter occupants, lighting, equipment, ventilation and infiltration without double counting outdoor airflow.
  3. Set unit count, equipment SHR and capacity factor at design conditions; inspect load components before selection.

Worked example

This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.

Examples use a decimal point and no thousands separator.

All example inputs
ParameterValue / interpretation
Floor area30 m²
Room height3 m
Indoor temperature24 °C
Indoor humidity50 %
Outdoor temperature35 °C
Outdoor humidity60 %
Atmospheric pressure101.325 kPa
Net opaque external wall area25 m²
Wall heat transfer coefficient1.8 W/m²K
Wall solar equivalent rise5 K
Exposed roof area0 m²
Roof heat transfer coefficient1 W/m²K
Roof solar equivalent rise15 K
External glazing area4 m²
Glazing heat transfer coefficient5.7 W/m²K
Incident solar irradiance400 W/m²
Solar heat fraction through glazing0.5
Solar fraction remaining after shading0.7
Occupants4 people
Sensible heat per person75 W
Latent heat per person55 W
Lighting power density10 W/m²
Equipment heat gain500 W
Simultaneous equipment use fraction1
Outdoor air entering room60 m³/h
Air changes per hour from infiltration0.3 1/h
Other sensible gains0 W
Other latent gains0 W
Design allowance10 %
Number of AC units1 units
Temperature-cooling / total cooling capacity ratio0.75
Actual / nameplate AC capacity ratio1

Expected results (rounded)

ParameterValue / interpretation
Sensible load2.93 kW
Latent load1.05 kW
Total load with allowance4.38 kW
Reference capacity per unit18000 BTU/h

Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.

Method & limitations

Single-room steady-state estimate, not hourly HB/RTS. BTU/h sizes are references; verify actual equipment sensible/latent capacities.

Steady-state heat-gain estimate, not hourly HB/RTS. Walls/roof: U·A·(Tout−Tin+ΔTsolar); glazing: U·A·ΔT + A·I·SHGC·Fshade. Solar equivalent rise is user-defined and is not derived from orientation, weather or design hour.

People: count × sensible/latent gain per person. Lighting: area × W/m². Equipment: heat gain × use factor. Outdoor-air total load uses dry-air mass flow × enthalpy difference; sensible load uses heat capacity at indoor humidity ratio, with latent load as the remainder. Cooler/drier outdoor air can produce negative components; aggregate sensible and latent loads are each floored at zero for sizing.

The allowance applies to both sensible and latent loads. The smallest reference BTU/h size meeting total, sensible and latent requirements is selected using unit count, assumed SHR and capacity factor. This does not replace manufacturer selection data or peak-load calculations with weather, thermal storage, solar orientation, thermal bridges and schedules. Floor/adjacent-zone, fan/duct and recovery effects are not calculated; use other gains as appropriate.

ASHRAE — Cooling load calculations

Common mistakes

Confusing cooling capacity with electrical input; including glazing in opaque wall area; substituting room SHR for equipment SHR; double counting ventilation.

Projects & reports

  1. Choose or create an engineering project and enter your actual design inputs.
  2. Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
  3. Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.

Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.

References & related tools

ASHRAE — Cooling Load

The tool implements the methods and limits stated above; linking a standard does not establish complete compliance with that standard.