ACMV Pro / Tool guide

TOOL GUIDE

Air grille sizing

Estimate outlet face sizes from equally divided airflow, free-area velocity and free-area ratio.

Purpose & scope

Estimate outlet face sizes from equally divided airflow, free-area velocity and free-area ratio.

Face-area sizing, not neck selection. Throw, NC, pressure drop and distribution require catalogue verification.

Inputs

Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.

ParameterValue / interpretation
Diffuser / grille typeLinear — elongated face / Rectangular grille / Circular diffuser / Square diffuser
Total airflow · m³/hVolumetric flow at the calculation location; check the selected unit.
Number of grillesPositive integer count of outlets sharing airflow equally.
Free-area velocity · m/sVelocity through grille free area, distinct from face velocity.
Free area / face area ratio · %Free-area to face-area ratio from catalogue data.
Quick reference face sizeReference face sizes. Check neck dimensions and free area against the catalogue.
Face width / length / diameter · mmGrille face width/length or circular face diameter, not neck size.
Grille face height · mmRectangular grille face height; square diffusers use the width for both sides.

Steps

  1. Select outlet type, total airflow and count.
  2. Enter catalogue free-area ratio and design velocity.
  3. Review candidates or check an existing face size; save the outlet group in the project.

Worked example

This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.

Examples use a decimal point and no thousands separator.

All example inputs
ParameterValue / interpretation
Diffuser / grille typeRectangular grille
Total airflow2400 m³/h
Number of grilles4
Free-area velocity2.5 m/s
Free area / face area ratio60 %
Quick reference face sizeCustom dimensions
Face width / length / diameter400 mm
Grille face height300 mm

Expected results (rounded)

ParameterValue / interpretation
Flow per outlet600 m³/h
Required face area per outlet0.1111 m²
First candidate450 × 250 mm

Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.

Method & limitations

Face-area sizing, not neck selection. Throw, NC, pressure drop and distribution require catalogue verification.

Free area = flow per grille / velocity. Face area = free area / free-area ratio. Flow is distributed equally among grilles.

60% is an example; replace it with catalogue data. Dimensions are nominal face sizes, not neck sizes or actual open area. Quick sizes are references and are not available from every manufacturer.

This is preliminary area sizing, not product selection. Check noise, throw, drop, pressure loss and air distribution in the manufacturer catalogue.

Square diffusers use equal sides; circular uses πD²/4; rectangular and linear use length × width. Linear sizing uses face area and the entered free-area ratio; it does not select slot count or slot width. Changing type does not change the free-area ratio.

Up to 10 smallest qualifying options are selected before column sorting. Square/circular: 50 mm increments, 100–2,000 mm; rectangular: 50 mm increments and aspect ratio ≤4. Linear: length 300–2,000 mm, width 50/75/100/150/200/250/300 mm, length/width ≥3. Options are geometric preliminary checks.

Common mistakes

Confusing face and free area; entering neck instead of face dimensions; failing to divide total airflow by outlet count.

Projects & reports

  1. Choose or create an engineering project and enter your actual design inputs.
  2. Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
  3. Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.

Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.

References & related tools

ASHRAE — Room Air Distribution

The tool implements the methods and limits stated above; linking a standard does not establish complete compliance with that standard.