Water pipe supports guide
Purpose
Calculate water pipe support loads, quantities, geometric spans and multi-segment project schedules.
Inputs
| Parameter | Value / interpretation |
|---|---|
| Support type | One pipe with one rod, or multiple pipe groups on a shared two-rod bearer. |
| Pipe dimensions | Choose SGP/Schedule 40 or enter outside diameter, wall and density. DN is not the actual diameter. |
| Water and insulation | Enter fluid density, insulation thickness and density, and the count of identical pipes. |
| Longitudinal support spacing | Entered by the user; verify against the design, materials and operating conditions. |
| Rod span and bearer | Automatic geometric fit or manual layout; this does not select a structural section. |
Steps
- Choose the support type and pipe groups using a preset or catalogue dimensions.
- Enter length, spacing, fluid, insulation and additional load.
- Review the geometric span and results, name the segment and save it to a project.
Worked example
Training example using the assumptions below; these are not mandatory specifications.
All example inputs
| Parameter | Value / interpretation |
|---|---|
| Length / spacing | 24 m / 3 m |
| SGP DN100 pipes | 2 × Ø114.3 × 4.5 mm |
| Insulation / density | 25 mm / 60 kg/m³ |
| Pipe / water density | 7850 / 1000 kg/m³ |
| Support mass / additional load | 3 kg / 0 kN |
| Rod length each | 1 m |
Expected results
| Parameter | Value / interpretation |
|---|---|
| Mass per route metre | 43.100 kg/m |
| Maximum support load | 1.297 kN |
| Sets / clamps / inserts / rods | 9 / 18 / 18 / 18 |
| Rod span / bearer cut length | 0.55 / 0.65 m |
| Total rod / bearer length | 18 / 5.85 m |
Method and limits
Pipe, fluid and insulation mass use annular or circular areas. Gravity load uses tributary length and support mass, plus additional load. The route is divided into equal bays no longer than the requested spacing, with supports at both ends.
Automatic span selection is geometric clearance only. Pipe/bearer bending, deflection, rods, anchors, insulation inserts, thermal stress and dynamic loads are not verified. Each saved segment includes both ends; supports at shared junctions are not merged.
Common issues
Single-pipe mode sets the count to one; shared mode restores the previous groups. Wall thickness must be less than half the outside diameter. Transfers from pipe sizing require outside diameter and wall confirmation; internal diameter cannot be used for pipe mass.
Save and report
Select or create a project, enter a segment code and add it to the schedule. Edit/delete up to 300 segments per project. Preview or print/PDF the current segment, schedule or full project. Back up using project JSON export.